Lesson 8 · Fire engineering

Fire engineering: standing up while it burns

A fire is rare but certain to happen somewhere, and when it does the structure has to hold up long enough for people to get out and firefighters to get in. Hot steel softens, hot concrete spalls, timber burns away: fire design is about how fast each one happens.

The standard fire

Real fires vary with what is burning and how much air gets in. To compare designs, codes use a standard fire: the ISO 834 gas temperature, rising fast at first and then more slowly, with \(t\) in minutes:

\[\theta_g = 20 + 345 \log_{10}(8t + 1)\ \ ^{\circ}\text{C}\]

It reaches about 840 °C at 30 minutes, 945 °C at 60, 1006 °C at 90 and 1049 °C at 120. A fire resistance of R60 means the member keeps carrying its load (R), and where needed stays intact (E) and insulating (I), for 60 minutes of this fire. Building regulations set the period from the building's height and use.

gas temperature, ISO 834 120 min0 1049 °C strength left (1.0 at the top) 1000 °C20 steel yield concrete
Left: the standard fire. Right: steel keeps its full yield strength to 400 °C, then loses it fast (about 47 % left at 600 °C); concrete loses strength more gradually, and its mass keeps the inside cool.

Steel gets weaker

Steel does not burn, but it conducts heat well and its strength falls quickly above 400 °C. The Eurocode reduction factor \(k_{y,\theta}\) is 1.0 up to 400 °C, 0.78 at 500 °C, 0.47 at 600 °C, 0.23 at 700 °C and 0.11 at 800 °C.

A member fails when its strength has dropped to the load it carries. If it is used at a fraction \(\mu_0\) of its cold capacity, Eurocode 3 gives the critical temperature directly:

\[\theta_{cr} = 39.19 \ln\!\left[\frac{1}{0.9674\, \mu_0^{3.833}} - 1\right] + 482\ \ ^{\circ}\text{C}\]

How fast the member gets there depends on its section factor \(A_m/V\): heated surface per unit volume. A thin, open section (high \(A_m/V\)) heats fast; a chunky one heats slowly. Protection (boards, sprayed coatings, intumescent paint that swells into an insulating foam) slows the heating so the critical temperature is reached after the required time.

Concrete and its cover

Concrete is a poor conductor, so a concrete member heats slowly from the outside in. The danger is to the reinforcement: it is steel, and it sits near the hot surface. Fire design of concrete is therefore mostly about minimum member sizes and the axis distance, the distance from the heated face to the centre of the bars, given in code tables for each fire period. Dense, wet, high-strength concrete can also spall, with surface layers bursting off and exposing the bars; polypropylene fibres in the mix help prevent it.

Timber chars

Timber burns, but large sections burn slowly and predictably. The outside turns to char, which insulates the wood behind it; just inside the char line the wood is still almost at room temperature. Softwood chars at about 0.65 mm/min on a flat face; to allow for rounded corners, design uses a slightly higher notional rate \(\beta_n\) (0.8 mm/min for solid softwood, 0.7 for glulam).

The reduced cross-section method of Eurocode 5 removes the char depth plus a 7 mm layer of heated, weakened wood, and checks what is left at full strength:

\[d_{\text{ef}} = \beta_n\, t + 7\ \text{mm}\]

Worked examples

Critical temperature of a steel beam

A steel beam uses half of its cold capacity, \(\mu_0 = 0.5\):

\[\theta_{cr} = 39.19 \ln\!\left[\frac{1}{0.9674 \times 0.5^{3.833}} - 1\right] + 482 = 39.19 \ln(13.75) + 482 \approx 585\ ^{\circ}\text{C}\]

The standard fire passes 585 °C in under 5 minutes, but the steel lags behind the gas. An unprotected beam with a high section factor can still reach 585 °C in 15 to 20 minutes, which is why steel usually needs protection for R60.

Glulam beam after 60 minutes

GL24h beam, 215 × 450 mm, exposed on both sides and the bottom (the slab protects the top). \(\beta_n = 0.7\ \text{mm/min}\):

\[\begin{aligned} d_{\text{ef}} &= 0.7 \times 60 + 7 = 49\ \text{mm} \\ b_{\text{fi}} &= 215 - 2 \times 49 = 117\ \text{mm}, \qquad h_{\text{fi}} = 450 - 49 = 401\ \text{mm} \\ \frac{W_{\text{fi}}}{W} &= \frac{117 \times 401^2}{215 \times 450^2} = 0.43 \end{aligned}\]

Only 43 % of the section modulus is left. But in fire the strength is taken without the cold-design reductions (\(f_{d,\text{fi}} = 1.15 f_k\) for glulam, against \(0.8 f_k / 1.25 = 0.64 f_k\) cold), so the bending resistance left is \(0.43 \times 1.15 / 0.64 \approx 0.78\) of the cold design value. The load in fire is typically about 0.6 of the cold design load (next section), so even a fully used beam survives 60 minutes.

The load in a fire

A fire is an accidental situation: the building is unlikely to be fully loaded at the same moment, and partial factors on loads drop to 1.0. The design load in fire is usually only 0.5 to 0.7 of the cold design load (Eurocode 5 lets you take 0.6 as a simple default). That reserve, together with the strength that fire design does not reduce, is what lets structures stand while they burn.

Intuition

Steel is like a thin pan: it heats through quickly, so it needs a coat. Concrete is like a thick stone: slow to heat, but watch the steel hidden near its surface. Timber is like a log on the fire: the outside burns, and the charred skin protects the core.