Lesson 9 · Earthquake engineering

Earthquake engineering: designing for a moving ground

An earthquake does not push on a building. It moves the ground underneath, and the building's own mass resists being dragged along. Understanding that one idea explains most of seismic design.

Inertia, not load

When the ground accelerates, every floor's mass resists with an inertia force \(F = m\,a\). Heavier buildings attract larger earthquake forces. That is why seismic design starts by keeping mass low, especially high up.

Natural period

Pull a building sideways and let go: it sways back and forth at its own rhythm. The time for one full sway is its natural period T. For a simple one-storey frame with mass m and lateral stiffness k:

\[\omega = \sqrt{\frac{k}{m}} \qquad T = \frac{2\pi}{\omega}\]

Stiff, low buildings have short periods (0.1–0.5 s); tall, flexible ones have long periods (a common rough estimate is 0.1 s per storey). The period decides how strongly a building responds to a given earthquake.

Response spectra

Imagine a row of simple oscillators with different periods, all shaken by the same earthquake. Plot the peak acceleration each one feels against its period: that is a response spectrum. Design codes give a smoothed version for each site.

0.0 0.5 1.0 1.5 2.0 2.5 3.0 0.0 0.2 0.4 0.6 0.8 1.0 1.2 TA TB SDS = 1.0 g SD1 / T Fixed base T = 0.31 s · Sa = 1.0 g Isolated T = 2.5 s · Sa = 0.2 g Period shift Period T (s) Spectral acceleration Sa (g)
Most ordinary buildings sit on the plateau, where response is greatest. Lengthening the period moves a building down the descending branch.

Read \(S_a\) at the building's period, multiply by its mass, and you have the elastic base shear: \(V = m\,S_a\).

Worked example

Base shear of a one-storey frame

Roof mass \(m = 50\ \text{t}\ (50\,000\ \text{kg})\), lateral stiffness \(k = 20\,000\ \text{kN/m}\). The site spectrum's plateau is \(S_a = 1.0\,g\).

\[\omega = \sqrt{\frac{20\,000\,000}{50\,000}} = 20\ \text{rad/s} \qquad T = \frac{2\pi}{20} = 0.31\ \text{s}\]

0.31 s lies on the plateau, so \(S_a = 1.0\,g = 9.81\ \text{m/s}^2\):

\[V_{\text{elastic}} = 50\,000 \times 9.81 = 490\ \text{kN}\]

The frame would have to resist its own weight sideways to stay elastic. The next section explains why codes let us design for much less.

Ductility and the behaviour factor

Designing every building to stay elastic in a rare earthquake would be very expensive. Instead, codes divide the elastic force by a behaviour factor (R in ASCE 7 and TBDY 2018, q in Eurocode 8), typically 3 to 8 for well-detailed systems:

\[V_{\text{design}} = \frac{V_{\text{elastic}}}{R}\]

The price is that the structure must be able to yield and deform many times past first yield without losing strength. That requires ductile detailing: closely spaced ties, confined concrete, strong columns and weak beams, and shear strength greater than flexural strength.

Be aware

R is not a safety factor. It is a promise that the structure will behave in a ductile way. A building designed with a high R but detailed poorly is the classic cause of earthquake collapse.

Base isolation

Base isolation puts flexible bearings (laminated rubber or curved sliders) between the building and its foundation. The period jumps to 2–4 s, far down the spectrum, so the superstructure feels a fraction of the acceleration. The trade-off is displacement, which is concentrated in the bearings.

Isolating the same frame

Isolators give \(T = 2.5\ \text{s}\), where the spectrum gives \(S_a \approx 0.2\,g\).

\[\begin{aligned} V &= 50\,000 \times 0.2 \times 9.81 = 98\ \text{kN} \qquad \text{(one fifth of 490 kN)} \\ \omega &= \frac{2\pi}{2.5} = 2.51\ \text{rad/s} \\ S_d &= \frac{S_a}{\omega^2} = \frac{1.96}{6.32} = 0.31\ \text{m} \end{aligned}\]

The building above barely moves relative to itself, while the bearings travel about 310 mm. A seismic gap (moat) around the building must allow for that.

Try it: see how earthquake combinations govern a design.Open load combinations